rishocast

Earthing voltage transformer

RPG-613N

○Single phase / Earthing

○For voltmeter / For relay

○Indoor use

RPG-613N
Type

Ratio

(V)

Insulation level

(kV)

Over voltage factor Availability
IEC-186 IEC 60044-2
IEC 61869-3
RPG-613N

3300/√3 / 110/√3 / 110/3(190/3)

6600/√3 / 110/√3 / 110/3(190/3)

7.2 / 20 / 60 1.9
(30s)
200 / 200VA
1.0 / 3P
Primary fuse specification
Type Rated current Rated voltage Breaking current
PL-G T1A 7.2 / 3.6kV 40kA
EVTs shall be disconnected from the circuit of switchboard when withstand voltage test.
RPG-613N

▼Connection diagram

▲Secondary only

▲With tertiary