HOME > Products > Epoxy cast resin electric device > Molcon
Cast resin Phase advance Capacitor "Molcon®"
--Epoxy cast resin electric device--
Top runner transformer
Amorphous transformer
Special purpose transformer
Other line ups
Transformer for Wind turbine
Cast resin type Phase advance capacitor
Serial reactor for phase advance capacitor
Discharge coil for phase advance capacitor
Current transformer
Voltage transformer/ VT for operation power supply
Hook rod for disconnect switch operation
Current limiting reactor
Small size reactor for power conditioner
Insulator & bushing
Detective insulator
Cast resin products for switch gear
Silicone rubber covered epoxy bushing
Earthquake resistant test
Full solid insulation
MOLCON has the unique insulation structure which capacitor elements are entirely molded with flame retardant Epoxy resin.
Properties
1) Excellent in fire prevention property
Capacitor elements are entirely molded with flame retardant epoxy resin. Therefore MOLCON is suitable for being installed in public establishments.
2) Environmentally friendly
MOLCON is free from such environmental pollutants as Insulating oil or from such greenhouse agent as SF6 gas.
3) Maintenance-free
MOLCON is free from checking oil leaks or rust.
4) Excellent in both Humidity and Water resistance
Re-operation, after being showered with fire-fighting water, can be performed through proper maintenance.
5) Excellent in protective performance
Fault detector istalled with MOLCON makes capacitor circuit be opened in case of abnormal current caused at an early stage of failure. False operation of detector caused by power-supply noise is also prevented. (Connecting diagram)
6) Harmonic resistant
Both MOLCON and Serial reactor(L=6%) have harmonic proof property of I5 =55%
7) Low loss and Energy-saving
Energy-saving operation can be performed with Low loss PP film used as dielectrics. Temperature rise can be also avoided.
8)Reinforceable against earthquakes
Optional screw holes on side handles are available to clamp capacitor's body.
Standard specification
Circuit voltage
6600V・3300V
Standard
JIS C 4902-1:2010
Model
REC type
Installation location
Indoor only
Lower than 1000m of altitude
Under relative humidity of 85%
Ambient temperature
-20~+50℃
(Lower than 45℃ a day /Lower than 35℃ a year)
Capacity tolerance
-5~+10% (at 20℃)
(Unbalanced ratio among each phase<108%)
Dissipation factor
Lower than 0.040% (at 20℃ / Rated voltage)
Maximum allowable voltage
Voltage
Magnification
Allowed time
1.10
Within 12 hours a day
1.15
Within 30 minutes a day
1.20
Within 5 minutes
1.30
Within a minute
*Over voltage application of more than 1.15 times of rating must be less than 200 times
through the life of a capacitor
Temperature raise
Lower than 25℃ ( at 35℃ / Rated voltage)
Discharge property
Less than 50V within 5 minutes after circuit release.
Insulating strength
6600V:22/60kV 3300V:16/45kV
Color
Red
Installation distance
Farther than 50mm
Protective equipment
Fault detector
Specifications
◆3000V,6600V/ 3-phase / Indoor use / Built-in discharge resistance / Abnormal current sensing terminal (L=6%)
Rated voltage
[V]
Frequency
[Hz]
Installed capacity
[kvar]
Rated capacity
[kvar]
Rated current[A]
Model
Outline drawing
Dimension [mm]
Mass
3300V
6600V
A
B
C
D
E
F
G
H
[kg]
7020
or
3510
50/60
10/12
10.6/12.8
1.75/2.10
0.875/1.05
REC-□1010S-06
A
420
132
595
395
50
115
309
520
29
15/18
16.0/19.1
2.62/3.15
1.31/1.57
REC-□1015S-06
420
132
595
395
50
115
309
520
28
20/24
21.3/25.5
3.50/4.20
1.75/2.10
REC-□1020S-06
420
132
595
395
50
115
309
520
26
25/30
26.6/31.9
4.37/5.25
2.19/2.62
REC-□1025S-06
B
520
132
595
495
50
135
408
520
43
30/36
31.9/38.3
5.25/6.30
2.62/3.15
REC-□1030S-06
520
132
595
495
50
135
408
520
42
50
50
53.2
8.75
4.37
REC-□5050S-06
520
132
690
495
50
135
408
615
45
75
79.8
13.1
6.56
REC-□5075S-06
C
705
132
690
680
50
197
595
615
62
100
106
17.5
8.75
REC-□5100S-06
705
132
755
680
50
197
595
680
66
150
160
26.2
13.1
REC-□5150S-06
D
640
242
755
615
100
168
531
680
107
60
50
53.2
8.75
4.37
REC-□6050S-06
B
520
132
595
495
50
135
408
520
38
75
79.8
13.1
6.56
REC-□6075S-06
C
705
132
595
680
50
197
595
520
52
100
106
17.5
8.75
REC-□6100S-06
705
132
690
680
50
197
595
615
60
150
160
26.2
13.1
REC-□6150S-06
D
640
242
690
615
100
168
531
615
99
About □ in the column of model.
3 is plugged in □ in case of 3300V products and 6 is plugged in □ in case of 6600V products.
◆3000V,6600V/ 3-phase / Indoor use / Built-in discharge resistance / Abnormal current sensing terminal (L=13%)
Rated voltage [V]
Frequency
[Hz]
Installed capacity
[kvar]
Rated capacity
[kvar]
Rated current[A]
Model
Outline drawing
Dimension [mm]
Mass
3300V
6600V
A
B
C
D
E
F
G
H
[kg]
7590
or
3790
50/60
10/12
11.5/13.8
1.75/2.10
0.875/1.05
REC-□1010S-13
A
420
132
595
395
50
115
309
520
29
15/18
17.2/20.7
2.62/3.15
1.31/1.57
REC-□1015S-13
420
132
595
395
50
115
309
520
28
20/24
23.0/27.6
3.50/4.20
1.75/2.10
REC-□1020S-13
420
132
595
395
50
115
309
520
26
25/30
28.7/34.5
4.37/5.25
2.19/2.62
REC-□1025S-13
B
520
132
595
495
50
135
408
520
43
30/36
34.5/41.4
5.25/6.30
2.62/3.15
REC-□1030S-13
520
132
595
495
50
135
408
520
42
50
50
57.5
8.75
4.37
REC-□5050S-13
520
132
690
495
50
135
408
615
45
75
86.2
13.1
6.56
REC-□5075S-13
C
705
132
690
680
50
197
595
615
62
100
115
17.5
8.75
REC-□5100S-13
705
132
755
680
50
197
595
680
66
150
172
26.2
13.1
REC-□5150S-13
D
640
242
755
615
100
168
531
680
107
60
50
57.5
8.75
4.37
REC-□6050S-13
B
520
132
595
495
50
135
408
520
38
75
86.2
13.1
6.56
REC-□6075S-13
C
705
132
595
680
50
197
595
520
52
100
115
17.5
8.75
REC-□6100S-13
705
132
690
680
50
197
595
615
60
150
172
26.2
13.1
REC-□6150S-13
D
640
242
690
615
100
168
531
615
99
About □ in the column of model.
3 is plugged in □ in case of 3300V products and 6 is plugged in □ in case of 6600V products.
◆220V,440V/ 3-phase / Indoor use / Built-in discharge resistance and Thermal fuse / Abnormal current sensing terminal (L=6%)
Outline grawing
Circuit
volage
[V]
Rated
voltage
[V]
Frequency
[Hz]
Installed capacity
[kvar]
Rated capacity
[kvar]
Rated current
[A]
Model
Dimension [mm]
Mass
A
B
C1
C2
C3
D
E
F
G
[kg]
220
234
50/60
10/12
10.6/12.8
26.2/31.5
REC-2201010206T
330
125
295
230
140
310
65
80
260
11
15/18
16.0/19.1
39.4/47.2
REC-2201015206T
330
125
330
265
190
310
65
80
260
14
20/24
21.3/25.5
52.5/63.0
REC-2201020206T
330
125
370
305
190
310
65
80
260
17
25/30
26.6/31.9
65.6/78.7
REC-2201025206T
330
125
405
340
240
310
65
80
260
20
30/36
31.9/38.3
78.7/94.5
REC-2201030206T
430
125
350
285
190
410
65
100
360
21
50
50
53.2
131
REC-2205050206T
430
125
475
410
280
410
65
100
360
33
60
50
53.2
131
REC-2206050206T
430
125
425
360
240
410
65
100
360
28
440
468
50/60
10/12
10.6/12.8
13.1/15.7
REC-4401010506T
330
125
295
230
140
310
65
80
260
11
15/18
16.0/19.1
19.7/23.6
REC-4401015506T
330
125
330
265
190
310
65
80
260
14
20/24
21.3/25.5
26.2/31.5
REC-4401020506T
330
125
370
305
190
310
65
80
260
17
25/30
26.6/31.9
32.8/39.4
REC-4401025506T
330
125
405
340
240
310
65
80
260
20
30/36
31.9/38.3
39.4/47.2
REC-4401030506T
430
125
350
285
190
410
65
100
360
21
50
50
53.2
65.6
REC-4405050506T
435
165
390
325
240
415
65
100
364
33
75
79.8
98.4
REC-4405075506T
435
165
500
435
280
415
65
100
364
47
100
106
131
REC-4405100506T
435
165
585
520
350
415
65
100
364
58
60
50
53.2
65.6
REC-4406050506T
435
165
350
285
190
415
65
100
364
27
75
79.8
98.4
REC-4406075506T
435
165
445
380
240
415
65
100
364
39
100
106
131
REC-4406100506T
435
165
500
435
280
415
65
100
364
44
(Caution)
(1)Please be sure to install MOLCON in combination with serial reactor of
L=6% or L=13%.
(2)Please care that surface temperature of MOLCON must be kept less than
50℃(Less than 45℃ a day) Therefore especially in summer ,please take
care about surface temperature if MOLCON is installed in cubicle
(3)Please care that each distance of MOLCON must be more than 50mm when
multiple installation.
(4)Please care that discharge coil also must be installed if frequent switching
should be done.
(5)Please be sure that fault detector must be connected between "X1,X2
terminal" of MOLCON and trip circuit of capacitor switch
*Product of 3300V class is also available
--Epoxy cast resin electric device--
Top runner transformer
Amorphous transformer
Special purpose transformer
Other line ups
Transformer for Wind turbine
Cast resin type Phase advance capacitor
Serial reactor for phase advance capacitor
Discharge coil for phase advance capacitor
Current transformer
Voltage transformer/ VT for operation power supply
Hook rod for disconnect switch operation
Current limiting reactor
Small size reactor for power conditioner
Insulator & bushing
Detective insulator
Cast resin products for switch gear
Silicone rubber covered epoxy bushing
Earthquake resistant test