RPG-41T / RPG-41TB |
○Single phase / Earthing
○For voltmeter / For relay
○Indoor use |
 |
Type |
Ratio
(V) |
Insulation level
(kV) |
Over voltage factor |
Applicable standard of production |
IEC-186 |
IEC 60044-2
IEC 61869-3 |
RPG-41T |
11000/√3 / 110/√3 |
12 / 28 / 75 |
1.9
(30s) |
200VA 1.0 |
- |
RPG-41TB |
300VA 1.0 |
100VA 1.0 |
|
Type |
Ratio |
Insulation level |
Over voltage factor |
Applicable standard of production |
IEC-186 |
IEC 60044-2
IEC 61869-3 |
RPG-41T |
11000/√3 / 110/√3 / 110/3(190/3) |
12 / 28 / 75 |
1.9
(30s) |
200 / 200VA
1.0 / 3P |
- |
RPG-41TB |
300 / 200VA
1.0 / 3P |
100 / 100VA
1.0 / 3P |
|
Primary fuse specification |
Type |
Rated current |
Rated voltage |
Breaking current |
PL-J |
T1A |
12kV |
40kA |
|
EVTs shall be disconnected from the circuit of switchboard when withstand voltage test. |

|
▲RPG-41T |
 |
▲RPG-41TB |
▼Connection diagram |
 |
 |
▲Secondary only |
▲With tertiary |