HOME > Products > Epoxy cast resin electric device > dischage coil
Discharge coil for Phase advanced capacitors
 |
For safety operation of Phase advanced capacitor |

▲Discharge coil |
- Electric charge remains in capacitor after disconnecting capacitor from capacitor circuit.
- In this state ,it is dangerous to reconnect capacitor to the circuit or to practice inspection or maintenance.
- With discharge coil connected to capacitor circuit,residual charge can be consumed instantly.
- We recommend you install Discharge coil in capacitor circuit for safety operation.

▲Connection example
To avoid excess voltage caused by serial reactor ,please be sure to connect discharge coil to supply side terminal of serial reactor. |

Click to enlarge
|
Specifications
Standard |
JIS C 4902-3 |
Installation location |
Indoor only |
Instllation altitude |
Less than 1000m |
Ambient temperature |
-20/B |
Insulation class |
E |
Number of phase |
3(V connection) |
Frequency |
50Hz/60Hz |
|
Discharge property
It takes less than five seconds until terminal voltage becomes less than 50V, after disconnecting a capacitor from circuit.
Number of discharge
- Every one minute:5-time
- Every 5-minutes:Continuous
|
Maximum allowable voltage
Voltage factor |
Allowable load time |
1.10 |
12-hour a day |
1.15 |
30-minute a day |
1.20 |
Within 5-minute |
1.30 |
Within a minute |
|
Type
Type |
Insulation level |
Circuit
Voltage |
Discharge capacity |
Capacity of
connected capacitor |
RD-601N |
16/45kV |
3300V |
1000kvar |
~1000kvar |
22/60kV |
6600V |
☆Customized product according to each use is also available
|
|