Step up transformer for Installatin in Nacelle of Wind generation
 |
 |
(Property)
- Light weight & Compact with Al coil.
- Excellent quake-resistance against Vibration caused by Power generator ,Transformer itself ,Earthquake or Typhoon.
- Excellent in crack resistance against installation in Cold district.
|
Specifications
Rated Capacity |
2700 kVA |
Rated primary voltage |
690 V |
Rated secondary voltage |
F36000/R34500/F33000/F31500 V |
Rated frequency |
60 Hz |
Connection |
Dyn11 |
Thermal class |
F |
Standard |
IEC 60076-11 |
Approximate dimension |
2390(W)×1100(D)×2100(H) |
Approximate mass |
6500kg |
|

▲Image of installation in nacelle |
Vibration test
Test condition |
Acceleration |
0.5~1.0G |
Vibration frequency |
5~100Hz |
Vibration direction |
Horizontal/X,Y
Vertical/Z |
Test result |
Appearance and Structure |
OK
(Peeling paint) |
Acceptance |
OK |
|
Crack resistance
Thermal cycle test was run under the following condition considering a
installation in cold district
- -20℃ ~ 120℃
- -40℃ ~ 120℃
- -50℃ ~ 120℃
Each 3-cycle/Total 216 hours
No crack was found out with mold coil
|