HOME > Products > Epoxy cast resin electric device > Epoxy resin insulator > 10kV Post insulator
 |
| Type |
EM-10
(EG40345)
Outline drawing |
EM-10A-4
(EG41713)
Outline drawing |
EM-10B3-4
(EG43399)
Outline drawing |
EM-10N
(EG40374)
Outline drawing |
EM-10NB3-2
(EG43403)
Outline drawing |
|
EL-10
(EG40257)
Outline drawing |
EL-10N
(EG40781)
Outline drawing |
| Test item |
Unit |
| Value |
Nominal voltage |
kV |
11 |
11 |
11 |
16.5 |
16.5 |
11 |
16.5 |
| Power-frequency withstand voltage |
kV |
28 |
28 |
28 |
36 |
36 |
28 |
36 |
| Impulse withstand voltage |
kV |
75 |
75 |
75 |
95 |
95 |
75 |
95 |
| Power-frequency flashover voltage※ |
kV |
70 |
70 |
60 |
85 |
70 |
80 |
80 |
| 50% impulse voltage※ |
kV |
120 |
120 |
95 |
125 |
105 |
120 |
135 |
Bending strength
(RT / 1min.) |
N |
5880 |
5880 |
5880 |
5880 |
5880 |
8820 |
8820 |
| Tensile failing load※ |
N |
19600< |
19600< |
19600< |
19600< |
19600< |
19600< |
19600< |
| Torsional failing load ※ |
N-m |
490< |
490< |
490< |
490< |
490< |
490< |
490< |
| Creepage distance |
mm |
172 |
172 |
172 |
225 |
225 |
160 |
190 |
| Installed height |
mm |
115 |
115 |
115 |
145 |
145 |
115 |
145 |
| Max.diameter |
mmΦ |
75 |
75 |
75 |
80 |
80 |
92 |
90 |
| Mass |
g |
1.2 |
0.9 |
0.8 |
1.7 |
1.1 |
1.9 |
2.0 |
|
| |
- The load was applied from +50mm point to the specimen with tightening all the screws of the bottom mounting in order to measure bending strength.
- Creepage distance shows the length from the upper end to the bottom end along the fin surface.
- ※=reference value
- The above items are designed to be installed in general power switchboards and not fit to be exposed to insulation gas.
|
| |