HOME > Products > Epoxy cast resin electric device > Epoxy resin insulator > 3kV Post insulator
 |
| Type |
RECL-22
(EG11459)
Outline drawing |
RECL-66-1
(EG11882)
Outline drawing |
RECL-66-2
(EG11879)
Outline drawing |
|
EM-3
(EG43735)
Outline drawing |
EM-3-2
(EG43373)
Outline drawing |
EL-3
(EG43360)
Outline drawing |
EL-3FR
(EG44389) Outline drawing |
| Test item |
Unit |
| Value |
Nominal voltage |
kV |
0.4 |
0.6 |
0.6 |
3.3 |
3.3 |
3.3 |
3.3 |
| Power-frequency withstand voltage |
kV |
- |
- |
- |
16 |
16 |
16 |
16 |
| Impulse withstand voltage |
kV |
- |
- |
- |
45 |
45 |
45 |
45 |
| Power-frequency flashover voltage※ |
kV |
30 |
30 |
30 |
40 |
30 |
40 |
- |
| 50% impulse voltage※ |
kV |
60 |
60 |
60 |
70 |
55 |
70 |
- |
Bending strength
(RT / 1min.) |
N |
2940 |
2450 |
2450 |
5880 |
5880 |
8820 |
8820 |
| Tensile failing load※ |
N |
7840< |
9800< |
9800< |
19600< |
19600< |
19600< |
29400< |
| Torsional failing load ※ |
N-m |
- |
- |
- |
490< |
440< |
490< |
- |
| Creepage distance |
mm |
- |
- |
- |
85 |
85 |
95 |
110 |
| Installed height |
mm |
40 |
50 |
50 |
60 |
60 |
60 |
70 |
| Max.diameter |
mmΦ |
40 |
(26×54) |
(26×54) |
70 |
70 |
82 |
80 |
| Mass |
g |
80 |
150 |
160 |
795 |
435 |
895 |
680 |
|
| |
- The load was applied from +50mm point to the specimen with tightening all the screws of the bottom mounting in order to measure bending strength.
- Creepage distance shows the length from the upper end to the bottom end along the fin surface.
- ※=reference value
- The above items are designed to be installed in general power switchboards and not fit to be exposed to insulation gas.
|
| |