HOME > Products > Epoxy cast resin electric device > Epoxy resin insulator > 60-70kV Post insulator

|
| Type |
EM-60
(EG40518)
Outline drawing |
EM-70
(EG40521)
Outline drawing |
| Test item |
Unit |
| Value |
Nominal voltage |
kV |
66 |
77 |
| Power-frequency withstand voltage |
kV |
140 |
160 |
| Impulse withstand voltage |
kV |
350 |
400 |
| Power-frequency flashover voltage※ |
kV |
200 |
260 |
| 50% impulse voltage※ |
kV |
390 |
435 |
Bending strength
(RT / 1min.) |
N |
5880 |
5880 |
| Tensile failing load※ |
N |
19600< |
19600< |
| Torsional failing load ※ |
N-m |
490< |
490< |
| Installed height |
mm |
680 |
780 |
| Max.diameter |
mmΦ |
174 |
150 |
| Mass |
g |
14.1 |
17.8 |
|
| |
- The load was applied from +50mm point to the specimen with tightening all the screws of the bottom mounting in order to measure bending strength.
- Creepage distance shows the length from the upper end to the bottom end along the fin surface.
- ※=reference value
- The above items are designed to be installed in general power switchboards and not fit to be exposed to insulation gas.
|
| |