HOME > Products > Epoxy cast resin electric device > Epoxy resin insulator > 6kV Post insulator
6kV Post insulator - Bending strenght 5880N / 8820N
 |
| Type |
EM-6
(EG44015)
Outline drawing |
EM-6A-4
(EG40622)
Outline drawing |
EM-6B-4
(EG43748)
Outline drawing |
EM-6B3-5
(EG43386)
Outline drawing |
|
EL-6
(EG40231)
Outline drawing |
EL-6FR
(EG44392)
Outline drawing |
| Test item |
Unit |
| Value |
Nominal voltage |
kV |
6.6 |
6.6 |
6.6 |
6.6 |
6.6 |
6.6 |
| Power-frequency withstand voltage |
kV |
22 |
22 |
22 |
22 |
22 |
22 |
| Impulse withstand voltage |
kV |
60 |
60 |
60 |
60 |
60 |
60 |
| Power-frequency flashover voltage※ |
kV |
60 |
60 |
50 |
50 |
69 |
- |
| 50% impulse voltage※ |
kV |
110 |
110 |
85 |
85 |
95 |
- |
Bending strength
(RT / 1min.) |
N |
5880 |
5880 |
5880 |
5880 |
8820 |
8820 |
| Tensile failing load※ |
N |
19600< |
19600< |
19600< |
19600< |
19600< |
29400< |
| Torsional failing load ※ |
N-m |
490< |
490< |
490< |
490< |
490< |
- |
| Creepage distance |
mm |
126 |
126 |
126 |
126 |
120 |
195 |
| Installed height |
mm |
90 |
90 |
90 |
90 |
90 |
100 |
| Max.diameter |
mmΦ |
75 |
75 |
75 |
75 |
86 |
85 |
| Mass |
g |
1.0 |
0.8 |
0.6 |
0.7 |
1.2 |
1.1 |
|
| |
- The load was applied from +50mm point to the specimen with tightening all the screws of the bottom mounting in order to measure bending strength.
- Creepage distance shows the length from the upper end to the bottom end along the fin surface.
- ※=reference value
- The above items are designed to be installed in general power switchboards and not fit to be exposed to insulation gas.
|
| |