HOME > Products > Epoxy cast resin electric device > Epoxy resin insulator > 6kV Post insulator
6kV Post insulator - Bending strenght 1765N / 7061N
 |
| Type |
JIS compliant
EID6A1
(EG10791)
Outline drawing |
JIS compliant
EID6A2
(EG10821)
Outline drawing |
|
EIH6A1
(EG11231)
Outline drawing |
EIH6A2
(EG11257)
Outline drawing |
| Test item |
Unit |
| Value |
Nominal voltage |
kV |
6.6 |
6.6 |
6.6 |
6.6 |
| Power-frequency withstand voltage |
kV |
22 |
22 |
22 |
22 |
| Impulse withstand voltage |
kV |
60 |
60 |
60 |
60 |
| Power-frequency flashover voltage※ |
kV |
55 |
55 |
55 |
55 |
| 50% impulse voltage※ |
kV |
90 |
90 |
90 |
90 |
Bending strength
(RT / 1min.) |
N |
1765 |
1765 |
7061 |
7061 |
| Tensile failing load※ |
N |
19600< |
19600< |
19600< |
19600< |
| Torsional failing load ※ |
N-m |
49< |
196< |
196< |
196< |
| Creepage distance |
mm |
110 |
110 |
112 |
112 |
| Installed height |
mm |
80 |
80 |
80 |
80 |
| Max.diameter |
mmΦ |
52 |
52 |
75 |
75 |
| Mass |
g |
345 |
340 |
726 |
718 |
|
| |
- The load was applied from +50mm point to the specimen with tightening all the screws of the bottom mounting in order to measure bending strength.
- Creepage distance shows the length from the upper end to the bottom end along the fin surface.
- ※=reference value
- The above items are designed to be installed in general power switchboards and not fit to be exposed to insulation gas.
|
| |