HOME > Products > Epoxy cast resin electric device > Epoxy resin insulator > 6kV Post insulator
Lightweight 6kV Post insulator / Bending strenght 2450N
 |
| Type |
JIS compliant
ES-6-J1
(EG44132)
Outline drawing |
JIS compliant
ES-6-J2
(EG44145)
Outline drawing |
ES-6-1
(EG43445)
Outline drawing |
ES-6-2
(EG43458)
Outline drawing |
ES-6-2X
(EG43432)
Outline drawing |
ES-6-3
(EG43429)Outline drawing |
| Test item |
Unit |
| Value |
Nominal voltage |
kV |
6.6 |
6.6 |
6.6 |
6.6 |
6.6 |
6.6 |
| Power-frequency withstand voltage |
kV |
22 |
22 |
22 |
22 |
22 |
22 |
| Impulse withstand voltage |
kV |
60 |
60 |
60 |
60 |
60 |
60 |
| Power-frequency flashover voltage※ |
kV |
50 |
50 |
50 |
50 |
50 |
50 |
| 50% impulse voltage※ |
kV |
90 |
90 |
90 |
90 |
90 |
90 |
Bending strength
(RT / 1min.) |
N |
2450 |
2450 |
2450 |
2450 |
2450 |
2450 |
| Tensile failing load※ |
N |
9800< |
9800< |
9800< |
9800< |
9800< |
9800< |
| Torsional failing load ※ |
N-m |
147 |
294 |
147 |
294 |
394 |
294 |
| Creepage distance |
mm |
110 |
110 |
110 |
110 |
110 |
110 |
| Installed height |
mm |
90 |
90 |
90 |
90 |
90 |
90 |
| Max.diameter |
mmΦ |
55 |
55 |
55 |
55 |
55 |
55 |
| Mass |
g |
345 |
350 |
345 |
350 |
350 |
360 |
|
| |
- The load was applied from +50mm point to the specimen with tightening all the screws of the bottom mounting in order to measure bending strength.
- Creepage distance shows the length from the upper end to the bottom end along the fin surface.
- ※=reference value
- The above items are designed to be installed in general power switchboards and not fit to be exposed to insulation gas.
|
| |